Hitachi Energy RTU500 Web Interface Vulnerability (CVE‑2026‑1772)

View CSAF Summary Hitachi Energy is aware of vulnerabilities that affect RTU500 product versions listed in this document. Successful exploitation of these vulnerabilities can result in the exposure of low-value user management information and device outage. Please refer to the Recommended Immediate Actions for information about the mitigation/remediation. The following versions of Hitachi Energy RTU500 Product are affected: RTU500 series CMU Firmware vers:RTU500_series_CMU_Firmware/>=12.7.1|<=12.7.7, vers:RTU500_series_CMU_Firmware/>=13.5.1|<=13.5.4, vers:RTU500_series_CMU_Firmware/>=13.6.1|<=13.6.2, vers:RTU500_series_CMU_Firmware/>=13.7.1|<=13.7.7, 13.8.1  CVSS Vendor Equipment Vulnerabilities v3 7.5 Hitachi Energy Hitachi Energy RTU500 Product Improper Handling of Insufficient Permissions or Privileges , Incomplete List of Disallowed Inputs, Uncontrolled Recursion, Allocation of Resources Without Limits or Throttling Background Critical Infrastructure Sectors: Critical Manufacturing Countries/Areas Deployed: Worldwide Company Headquarters Location: Switzerland Vulnerabilities Expand All + CVE-2026-1772 RTU500 web interface: An unprivileged user can read user management information. The information cannot be accessed via the RTU500 web user interface but requires further tools like browser development utilities to access them without required privileges...

Verisq™ Intelligence · 📅 March 05, 2026 · 📰 cisa.gov
🟠
Severity
High
VU
Type
Vulnerability
🎯
Confidence
High
🏢
Affected
2 sector(s)
✅
Actions
5 recommended
📰
Source
cisa.gov

LiveThreat Vulnerability Brief — CVE‑2026‑1772

What It Is — Hitachi Energy’s RTU500 remote‑terminal‑unit series contains a web‑interface flaw that permits an unauthenticated user to read low‑value user‑management data and, under certain conditions, trigger a device outage. The vulnerability scores 7.5 (CVSS v3.1 – High) and is publicly disclosed with a proof‑of‑concept that leverages browser developer tools. Exploitability — PoC available; active exploitation not yet reported in the wild.

Affected Products — Hitachi Energy RTU500 series firmware versions 12.7.1‑12.7.7, 13.5.1‑13.5.4, 13.6.1‑13.6.2, 13.7.1‑13.7.7, and 13.8.1.

TPRM Impact — The RTU500 is deployed in critical manufacturing and energy‑utility environments worldwide; a breach could expose internal user‑management details and cause localized outages, propagating risk to downstream suppliers and service providers that rely on uninterrupted process control.

Recommended Actions — 1️⃣ Deploy the latest firmware (≥ 13.8.2) or apply vendor‑issued patches. 2️⃣ Restrict web‑UI access to trusted IP ranges and enforce network segmentation. 3️⃣ Enable multi‑factor authentication for any privileged UI accounts. 4️⃣ Monitor for anomalous HTTP requests to the RTU500 UI and log all access attempts. 5️⃣ Conduct a rapid inventory of all RTU500 deployments and verify version compliance. Source: CISA Advisory ICS‑A‑26‑062‑03

📰 Original Source
https://www.cisa.gov/news-events/ics-advisories/icsa-26-062-03 ↗