High severity · published Jul 26, 2023
CVE-2022-4608
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product
7.5
CVSS
0.7%
EPSS
No
On KEV
Description
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.
CVSS vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
None
Confidentiality
None
Integrity
None
Availability
High
Scope
Unchanged
Exploitation
Is it being used?
Exploit prediction (EPSS)0.7% · higher than 53% of CVEs
Exploited in the wildNo evidence yet
CISA KEVNot listed
Ransomware campaign useNot known
Affected products
Which versions
RF
Rtu500 Firmware · Hitachienergy
13.3.1; 13.3.2; 13.3.3; 13.4.1 · source: NVD
Affected product
RF
Rtu500 Firmware
Hitachienergy
More from Rtu500 Firmware
7.5
CVE-2023-6711
Vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below
7.5
CVE-2022-2502
A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product
7.5
CVE-2022-3353
A vulnerability exists in the IEC 61850 communication stack that affects multiple Hitachi Energy products.  An attacker could exploit the vulnerability by using a specially…
7.5
CVE-2022-28613
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above
7.5
CVE-2021-35533
Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an…