High severity · published Jul 9, 2018
CVE-2018-4858
A vulnerability has been identified in IEC 61850 system configurator (All versions < V5.80), DIGSI 5 (affected as IEC 61850 system configurator is incorporated) (All versions <…
7.8
CVSS
1.8%
EPSS
No
On KEV
Description
A vulnerability has been identified in IEC 61850 system configurator (All versions < V5.80), DIGSI 5 (affected as IEC 61850 system configurator is incorporated) (All versions < V7.80), DIGSI 4 (All versions < V4.93), SICAM PAS/PQS (All versions < V8.11), SICAM PQ Analyzer (All versions < V3.11), SICAM SCC (All versions < V9.02 HF3). A service of the affected products listening on all of the host's network interfaces on either port 4884/TCP, 5885/TCP, or port 5886/TCP could allow an attacker to either exfiltrate limited data from the system or to execute code with Microsoft Windows user permissions. Successful exploitation requires an attacker to be able to send a specially crafted network request to the vulnerable service and a user interacting with the service's client application on the host. In order to execute arbitrary code with Microsoft Windows user permissions, an attacker must be able to plant the code in advance on the host by other means. The vulnerability has limited impact to confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.
CVSS vector
CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H
Attack vector
Local
Complexity
Low
Privileges
None
User interaction
Required
Confidentiality
High
Integrity
High
Availability
High
Scope
Unchanged
Exploitation
Is it being used?
Exploit prediction (EPSS)1.8% · higher than 78% of CVEs
Exploited in the wildNo evidence yet
CISA KEVNot listed
Ransomware campaign useNot known
Affected products
Which versions
D4
Digsi 4 Firmware · Siemens
All versions, or not specified · source: NVD
D5
Digsi 5 Firmware · Siemens
before 7.80 · source: NVD
SP
Sicam PQ Analyzer Firmware · Siemens
before 3.11 · source: NVD
SP
Sicam Pas/pqs · Siemens
before 8.11 · source: NVD
SS
Sicam Scc Firmware · Siemens
All versions, or not specified · source: NVD