Medium severity · published Mar 20, 2018
CVE-2018-4843
A vulnerability has been identified in SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU…
6.5
CVSS
0.5%
EPSS
No
On KEV
Description
A vulnerability has been identified in SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC CP 343-1 (incl. SIPLUS variants) (All versions), SIMATIC CP 343-1 Advanced (incl. SIPLUS variants) (All versions), SIMATIC CP 443-1 (All versions < V3.3), SIMATIC CP 443-1 (All versions < V3.3), SIMATIC CP 443-1 Advanced (All versions < V3.3), SIMATIC ET 200pro IM154-8 PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200pro IM154-8F PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200pro IM154-8FX PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200S IM151-8 PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200S IM151-8F PN/DP CPU (All versions < V3.2.16), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V1.7.0), SIMATIC S7-1500 Software Controller (All versions < V1.7.0), SIMATIC S7-300 CPU 314C-2 PN/DP (All versions < V3.3.16), SIMATIC S7-300 CPU 315-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 315F-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 315T-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317F-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317T-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317TF-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 319-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 319F-3 PN/DP (All versions < V3.2.16), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.7), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.1), SIMATIC WinAC RTX 2010 (All versions < V2010 SP3), SIMATIC WinAC RTX F 2010 (All versions < V2010 SP3), SINUMERIK 828D (All versions < V4.7 SP6 HF1), SIPLUS ET 200S IM151-8 PN/DP CPU (All versions < V3.2.16), SIPLUS ET 200S IM151-8F PN/DP CPU (All versions < V3.2.16), SIPLUS NET CP 443-1 (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (All versions < V3.3), SIPLUS S7-300 CPU 314C-2 PN/DP (All versions < V3.3.16), SIPLUS S7-300 CPU 315-2 PN/DP (All versions < V3.2.16), SIPLUS S7-300 CPU 315F-2 PN/DP (All versions < V3.2.16), SIPLUS S7-300 CPU 317-2 PN/DP (All versions < V3.2.16), SIPLUS S7-300 CPU 317F-2 PN/DP (All versions < V3.2.16), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), Softnet PROFINET IO for PC-based Windows systems (All versions). Responding to a PROFINET DCP request with a specially crafted PROFINET DCP packet could cause a denial of service condition of the requesting system.
The security vulnerability could be exploited by an attacker located on the same Ethernet segment (OSI Layer 2) as the targeted device. A manual restart is required to recover the system.
CVSS vector
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Attack vector
Adjacent
Complexity
Low
Privileges
None
User interaction
None
Confidentiality
None
Integrity
None
Availability
High
Scope
Unchanged
Exploitation
Is it being used?
Exploit prediction (EPSS)0.5% · higher than 45% of CVEs
Exploited in the wildNo evidence yet
CISA KEVNot listed
Ransomware campaign useNot known
Affected products
Which versions
SC
Simatic CP 343-1 Firmware · Siemens
All versions, or not specified · source: NVD
SC
Simatic CP 443-1 Firmware · Siemens
All versions, or not specified · source: NVD
SS
Simatic S7-1500 Firmware · Siemens
before 1.7.0 · source: NVD
SS
Simatic S7-300 Firmware · Siemens
All versions, or not specified · source: NVD
SS
Simatic S7-400 H V6 Firmware · Siemens
All versions, or not specified · source: NVD
SS
Simatic S7-400 Pn/dp V6 Firmware · Siemens
before 6.0.7 · source: NVD
SS
Simatic S7-400 Pn/dp V7 Firmware · Siemens
All versions, or not specified · source: NVD
SS
Simatic S7-410 Firmware · Siemens
before 8.1 · source: NVD
SW
Simatic Winac Rtx 2010 Firmware · Siemens
All versions, or not specified · source: NVD
S8
Sinumerik 828d Firmware · Siemens
All versions, or not specified · source: NVD
SP
Softnet Pn-io Linux Firmware · Siemens
All versions, or not specified · source: NVD
References
NVD
https://nvd.nist.gov/vuln/detail/CVE-2018-4843
CVE.org
https://www.cve.org/CVERecord?id=CVE-2018-4843
Vendor Advisory
https://cert-portal.siemens.com/productcert/pdf/ssa-592007.pdf
More from Simatic CP 343-1 Firmware
8.8
CVE-2016-8673
A vulnerability has been identified in SIMATIC CP 343-1 Advanced (incl
7.5
CVE-2023-51440
A vulnerability has been identified in SIMATIC CP 343-1 (6GK7343-1EX30-0XE0) (All versions), SIMATIC CP 343-1 Lean (6GK7343-1CX10-0XE0) (All versions), SIPLUS NET CP 343-1…
7.5
CVE-2021-33737
A vulnerability has been identified in SIMATIC CP 343-1 (incl
7.5
CVE-2019-13946
Profinet-IO (PNIO) stack versions prior V06.00 do not properly limit internal resource allocation when multiple legitimate diagnostic package requests are sent to the DCE-RPC…
5.3
CVE-2016-8672
A vulnerability has been identified in SIMATIC CP 343-1 Advanced (incl