Critical severity · published Apr 6, 2017
CVE-2017-7574
Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability
9.8
CVSS
1.3%
EPSS
No
On KEV
Description
Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product.
CVSS vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
None
Confidentiality
High
Integrity
High
Availability
High
Scope
Unchanged
Exploitation
Is it being used?
Exploit prediction (EPSS)1.3% · higher than 70% of CVEs
Exploited in the wildNo evidence yet
CISA KEVNot listed
Ransomware campaign useNot known
Affected products
Which versions
MT
Modicon Tm221ce16r Firmware · Schneider-electric
1.3.3.3 · source: NVD
SO
Somachine · Schneider-electric
1.4 · source: NVD
References
NVD
https://nvd.nist.gov/vuln/detail/CVE-2017-7574
CVE.org
https://www.cve.org/CVERecord?id=CVE-2017-7574
Vendor Advisory
http://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2017-097-01
Third Party Advisory
http://www.securityfocus.com/bid/97518
Broken Link
https://os-s.net/advisories/OSS-2017-02.pdf
More from Modicon Tm221ce16r Firmware
9.8
CVE-2017-7575
Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection password via a \x00\x01\x00\x00\x00\x05\x01\x5a\x00\x03\x00…